Manual abstract: user guide TOSHIBA RAS-10LKXSERVICE MANUAL
Detailed instructions for use are in the User's Guide.
[. . . ] HOW TO REPLACE THE MAIN PARTS
11-1 Indoor Unit 11-2 Microcomputer 11-3 Outdoor Unit
12. EXPLODED VIEWS AND PARTS LIST
12-1 12-2 12-3 12-4 12-5 12-6 12-7 12-8 12-9 Indoor Unit (E-Parts Assy) Indoor Unit (For RAS-10, 13, 16GKV-E2 / NKV-E2) Indoor Unit (For RAS-10, 13NKVX-T) Outdoor Unit (For 10 Series) Outdoor Unit (For 13 Series) Outdoor Unit (For 16 Series) Outdoor Unit (E-Parts Assy) (For 10 Series) Outdoor Unit (E-Parts Assy) (For 13 Series) Outdoor Unit (E-Parts Assy) (For 16 Series)
-2-
1. Specifications
RAS-10LKX / RAS-10GAV-E2, RAS-10NKV-A2 / RAS-10NAV-A2
Unit model
FILE NO. SVM-06032
RAS-10LKX / RAS-10GAV-E2 RAS-10NKV-A2 / RAS-10NAV-A2
(kW) (kW) (kW) (kW) Operation mode Running current Power consumption Power factor Operation mode Running current Power consumption Power factor 2. 5 0. 9 - 3. 0 3. 2 0. 9 - 4. 0 220- 240V- 1Ph- 50Hz Cooling Heating 0. 15 0. 15 30 30 87 87 Cooling Heating 3. 33 3. 69 730 810 95 95 3. 29/3. 81 38/39 34/35 27/29 46/47 RAS-10LKX, RAS-10NKV-A2 275 790 218 10 20 540/610 RAS-10GAV-E2, RAS-10NAV-A2 530 660 240 30 750
Cooling capacity Cooling capacity range Heating capacity Heating capacity range Power supply Indoor Electric characteristics Outdoor
(A) (W) (%) (A) (W) (%)
COP (Cooling / Heating) Operation noise Indoor
High (Cooling / Heating) (dB A) Medium (Cooling / Heating) (dB A) Low (Cooling / Heating) (dB A) Outdoor (Cooling / Heating) (dB A) Indoor unit Unit model Dimension Height (mm) Width (mm) Depth (mm) Net weight (kg) Fan motor output (W) Air flow rate (Cooling / Heating) (m3/h) Outdoor unit Unit model Dimension Height (mm) Width (mm) Depth (mm) Net weight (kg) Compressor Motor output (W) Type Single rotary type with DC-inverter variable speed control Model DA89X1F-23FZ Fan motor output (W) 20 Air flow rate (Cooling / Heating) (m3/h) 1320/1320 Piping connection Type Flare connection Indoor unit Liquid side 6. 35 Gas side 9. 52 Outdoor unit Liquid side 6. 35 Gas side 9. 52 Maximum length (Per unit) 10 (m) Maximum chargeless length (m) 10 Maximum height difference (m) 8 Refrigerant Name of refrigerant R410A Weight (kg) 0. 64 Wiring connection Power supply 3 Wires:includes earth (Outdoor) Interconnection 4 Wires:includes earth Usable temperature range Indoor (Cooling / Heating) (C) 21 - 32 / Up to 27 C Outdoor (Cooling / Heating) (C) 15 - 43 / - 10 - 24
The specification may be subject to change without nitice for purpose of improvement.
3
FILE NO. [. . . ] After determining the pipe hole position on the mounting plate (A), drill the pipe hole (65 mm) at a slight downward slant to the outdoor side. NOTE: When drilling a wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold separately. <Mounting the installation plate>
Anchor bolt holes
62 82. 5
Hook
2 m or more from floor
170 85
Indoor unit
7m
Indoor unit 5
m
45
75
45
*7m
m
1
Pipe hole Hook Thread Weight Hook Pipe hole
Installation plate
Remote Reception control range
Reception range * : Axial distance
Remote control
Indoor unit
7 Mounting screw
Fig. SVM-06032
<When the installation plate is directly mounted on the wall> 1. Securely fit the installation plate onto the wall by screwing it in the upper and lower parts to hook up the indoor unit. To mount the installation plate on a concrete wall with anchor bolts, utilize the anchor bolt holes as illustrated in the above figure. The supply voltage must be the same as the rated voltage of the air conditioner. NOTE: Wire type : More than H07RN-F or 245 IEC66 (1. 0 mm2 or more)
CAUTION
When installing the installation plate with a mounting screw, do not use the anchor bolt hole. Otherwise the unit may fall down and result in personal injury and property damage.
Installation plate <Keep horizontal direction>
CAUTION
This appliance can be connected to the mains in either of the following two ways. (1) Connection to fixed wiring : A switch or circuit breake which disconnects all poles and has a contact separation of at least 3 mm must be incorporate in the fixed wiring. (2) Connection with power supply plug : Attach power supply plug with power cord and plug it into wall outlet. 9-2-11 2) Firmly insert drains cap.
To connect the pipe after installation of the unit (figure)
(To the forefront of flare)
270 mm
No gap Do not apply lubricating oil (refrigerant machine oil) when inserting the drain cap. Application causes deterioration and drain leakage of the plug.
43 mm
Liquid side Gas side
170 mm
Outward form of indoor unit
R 30 mm or less (6. 35) R 40 mm or less (9. 52) (Use polisin (polyethylene core) or the like for bending pipe. )
Insert a hexagon wrench (4 mm)
Fig. 9-2-12
80
CAUTION
Firmly insert the drain hose and drain cap; otherwise, water may leak.
Use the handle of screwdriver, etc.
Fig. 9-2-15
NOTE: If the pipe is bent incorrectly, the indoor unit may <In case of right or left piping> After scribing slits of the front panel with a knife or a unstably be set on the wall. making-off pin, cut them with a pair of nippers or an After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes equivalent tool. and wrap the facing tape around them.
CAUTION
Bind the auxiliary pipes (two) and connecting cable with facing tape tightly. In case of leftward piping and rear-leftward piping, bind the auxiliary pipes (two) only with facing tape.
Slit
Fig. 9-2-13 <In case of bottom right or bottom left piping> After scribing slits of the front panel with a knife or a making-off pin, cut them with a pair of nippers or an equivalent tool.
Auxiliary pipes
Indoor unit Connecting cable
Installation plate
Fig. 9-2-16 Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit. Carefully connect the auxiliary pipes and connecting pipes to each other and cut off the insulating tape wound on the connecting pipe to avoid double-taping at the joint, moreover, seal the joint with the vinyl tape, etc. Since dewing results in a machine trouble, make sure to insulate both the connecting pipes. [. . . ] 3) When replacing the sensor using the colored protective tube, wind the color tape matching the color of that tube.
Thermal sensor part
Remarks
Cutting here 100
Connector
200
Cutting here
Common service parts of sensor TO, TS, TE, TD
15 70
Thermal constringent tube
Cutting here 100
15 70
Soldered part
Dryer
Winding the color tape
These are parts for servicing sensors. Please check that the accessories shown in the right table are packed. 1 2 3 4 5 6 Sensor
Part name
Q'ty 1 1 1 3 1 3 Length: 3 m For spare For spare
Remarks
Sensor Spring (A) Sensor Spring (B) Thermal constringent tube Color tape Terminal
Including one spare 9 colors
104
FILE NO. Indoor Unit (E-Parts Assy)
405
406
403 402
404 401
Location No. [. . . ]