If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual DANFOSS ECL CONFORT H66. We hope that this DANFOSS ECL CONFORT H66 user guide will be useful to you.
Manual abstract: user guide DANFOSS ECL CONFORT H66
Detailed instructions for use are in the User's Guide.
[. . . ] www. danfoss. com
VI. KM. T2. 02 2006. 12
www. danfoss. com
H66
*VIKMT202*
*087R8175*
ECL Comfort User's Guide
Installer's Guide
H66
VI. KM. T2. 02 2006. 12
Mixing and DHW controller
ECL Comfort Installer's Guide
*087R8175* *VIKMT202*
User's Guide
Controller mode Manual operation (used only at maintenance and service) Scheduled operation Constant comfort temperature Constant setback temperature Standby mode Arrow buttons. Circuit selector for switching between the circuits.
Display indications, controlled units, H66
1 ON 1 2 3 ON
A
B
C
D
A: P1 B: M1 C: M2 D: P3
Blank = OFF = Opens = Opens Blank = OFF
ON = ON = Closes
ON = ON
Safety Note To avoid injury of persons and damages to the device, it is absolutely necessary to read and observe these instructions carefully. Necessary assembly, start-up, and maintenance work must be performed by qualified and authorized personnel only.
This guide is associated with ECL Card 087B4974 Installer: By: Date:
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
= Closes
If the system you are about to install differs from the shown diagram of a standard heating system, feel free to sketch an outline for comparison. Adaptation of systems, see section 10.
S2
S1
ECL Comfort 301
List of components:
Room temperature sensor
Circuit indicator
Circuit Shift selector button
Adjust- Controller ment mode
M2 M1 P3 P1 S6 S5 S4 S3
Motorized control valve, circuit II Motorized control valve, circuit I Circulation pump, DHW, circuit II Circulation pump, heating, circuit I DHW return temperature sensor, circuit II DHW flow temperature sensor, circuit II Return temperature sensor, circuit I Flow temperature sensor, circuit I Outdoor temperature sensor
Table of Contents
Sections in the Installer's Guide
The documentation for the ECL Comfort controller is composed of numbered sections. [. . . ] 10: The setback temperature depends on the outdoor temperature, when the outdoor temperature is above the set limit. The lower the outdoor temperature, the less the temperature reduction. When the outdoor temperature is below the set limit, there is no temperature reduction. OFF: The setback temperature does not depend on the outdoor temperature.
Reduction
Extended service
100%
0% -29 -20 -10 0 10 20
Outdoor temperature °C
Setting line 11
The grey side of the ECL Card
The grey side of the ECL Card
32b
Circuit
Service parameter(s) 12-13
Service parameter(s) 14-15
14 Optimizing time constant
32c
Factory setting
12 Boost Setting range Factory setting I 0 . . . 99% 0% Shortens the heating-up period by increasing the desired flow temperature by the percentage you set.
Circuit
Setting range
Set the percentage at which you want the desired flow temperature increased temporarily. In order to shorten the heating-up period after a setback temperature period, the desired flow temperature can be increased temporarily (max. At optimizing the boost is active in the optimization period (line 14). If a room temperature sensor or an ECA 60 / 61 / 62 / 63 is connected, the boost stops when the room temperature has been reached. The boost also stops at the end of an optimizing period.
13 Reference ramping Circuit Setting range Factory setting I 0 . . . The time in which the desired flow temperature increases slowly to avoid load peaks in the heat supply.
I OFF / 10 . . . 59 OFF Optimizes the start and stop times for the comfort temperature period to obtain the best comfort at the lowest energy consumption. The lower the outdoor temperature, the earlier the heating cut-in.
Adjust the optimizing time constant. The two digits have the following meaning:
Digit 1 1 2 3 4 5 Digit 2 0 1 · 5 · 9 Heat accumulation of the building light medium heavy medium heavy Dimensioning temperature - 50 °C - 45 °C · - 25 °C · - 5 °C Floor heating systems Capacity large · · normal · small System type Radiator systems
Set the ramping time for the controller.
Temperature °C
OFF: No optimization. The heating starts and stops at the times set in the schedule.
Dimensioning temperature: The lowest outdoor temperature (usually determined by your system designer in connection with the design of the heating system) at which the heating system can maintain the designed room temperature.
Setting line 13
Time (min. )
Extended service
Extended service
In order to avoid load peaks in the supply network, the flow temperature can be set to increase slowly after a period with setback temperature. This causes the valve to open slowly.
15 Adaptive function of room temperature Circuit Setting range Factory setting I OFF / 1 . . . 30 OFF Controls how fast the room temperature adapts to the desired room temperature.
The adaptive funtion will eliminate the difference between the desired and the actual room temperature. This is done by integrating the difference and adjusting the desired flow temperature. The desired temperature is adapted slowly.
The grey side of the ECL Card
The grey side of the ECL Card
32d
Circuit
Service parameter(s) 17-20
Service parameter(s) 21
21 Total stop Circuit Setting range
32e
Factory setting OFF
17 Influence on desired flow temperature (Tflow. ref(I)) Setting range Factory setting I OFF / 1 . . . 20 K OFF The desired flow temperature in heating circuit I can be influenced by an external reference.
I ON / OFF Decide whether you want a total stop during the setback temperature period.
OFF: The desired flow temperature in circuit I is not influenced by any other controller (slave or circuit II). 20: The desired flow temperature is increased by the set value (line 17), if the demand of a slave / circuit II is higher.
Temp. Setting line 17
ON:
The desired flow temperature is lowered to 10 °C. setting of the flow temperature (line 2, section 22) is overruled.
Desired flow temp. [. . . ] The temperature is controlled according to your schedule with automatic changeover to / from comfort and setback temperature periods. In the DHW circuit, however, the DHW temperature is controlled according to the setback temperature.
The setting of the desired room temperature is important even if a room temperature sensor / room panel / remote control is not connected. Make sure that the radiator thermostat does not limit the room temperature. If you still cannot obtain the desired room temperature by adjusting the radiator thermostats, the flow temperature is too low. [. . . ]